MODEL P25C Differential Gage, Absolute, and Vacuum Transducer

The Model P25C pressure transducer provides high accuracy and reliability at a low cost. With a 4 to 20 mA output, the Model P25C is ideal for applications requiring a two wire transducer.


HIGH ACCURACY
HIGH STABILITY
INPUT/OUTPUT OPTIONS
LOW POWER CONSUMPTION
 
GENERAL SPECIFICATIONS
Pressure Ranges:
Absolute
Gage
Differential
Vacuum
Overpressure
* Line Pressure (diff. units)


Weight
Sensor Type
Media
 

0 to 1.0 psi through 0 to 1000 psi
0 to 2 H2O through 0 to 1000 psi
0 to 2 H2O through 0 to 500 psi
30 Hg through N/A
20 psi or 200% Full pressure range
350 psi Full scale of 5 psi or less. 800 psi ˜ Full scale greater than 5 psi
*Some change in zero and sensitivity can be expected
25 oz nominal
Variable Reluctance
Non corrosive liquids or gases in either or both pressure ports
 
ELECTRICAL
Input Voltage
Output
Output Noise
Insulation Resistance
Adjustment Range:
Zero
Span
 
12 to 50 VDC
4 to 20 mA
0.3% F.S. max.
100 megohms at 100 VDC min.

± 5.0% F.S. min.
± 5.0% F.S. min.
 
PERFORMANCE
Static Error Band *
Temperature Error *
Regulation
Resolution
 
± 0.3% F.S. max.
± 2.0% F.S. max.
0.001% F.S./Volt max.
Infinite
 
ENVIRONMENTAL
Temperature Range: *
Operating
Compensated
Humidity, Rain, Fungus,
Sand, and Dust
 

-65 F to 225 F
30 F to 130 F

Unaffected

*Static Error Band is defined as the maximum allowed deviation from a best fit straight line which minimizes errors due to non-linearity, hysteresis, resolution, and non-repeatability.
 
*Temperature Error is defined as the maximum allowed deviation from a best fit straight line which minimizes errors due to temperature over the range of + 30 F to + 130 F.
 
*Higher temperature operation may be supplied. Consult factory for special requirements.