MODEL P16C Very Low Differential Pressure Transducer

Typical applications include air conditioning control systems, air flow control measurements, and positive air pressure control systems. This unit is also available with an output proportional to the square root of the measured differential pressure for use in flow measurements.


VERY LOW DIFFERENTIAL
GAS PRESSURE MEASUREMENTS
HIGH ACCURACY
HIGH RELIABILITY
LONG TERM STABILITY
 
GENERAL SPECIFICATIONS
Pressure Ranges
Proof Pressure
Line Pressure
Weight
Sensor Type
Media
Porting
Housing
 
0 through 0.5” H2OD to 350 psid
10 psid or 2 x FSC whichever is greater
20 psid or 150% FSC whichever is greater
6.5 lbs max.
Variable reluctance
Clean, non corrosive gases
1/8” - NPT with integral filters
Water tight, dust tight steel with gray enamel paint
 
ELECTRICAL
Input Voltage
Output
Load Resistance
 
17 to 37 VDC (see graph)
4 to 20 mA linear with pressure
See Graph
 
PERFORMANCE
Linearity
Temperature
Hysteresis
Repeatability *
Resolution
Response Time
Adjustment Range:
Zero **
Span
 

± 0.5% F.S.
± 0.04% F.S./˚F max.
Negligible
± 0.1% F.S. max.
Infinite
50 ms max. to 63% of a step input

-2% to + 52% F.R.
20% to 100% F.R.

 
ENVIRONMENTAL
Temperature Range
 
0˚F to 130˚F
   
LOAD GRAPH
   

* Instability with time, zero shift with temperature and acceleration response are inversely proportional to the full scale setting i.e. at 40% rated range as full scale. They are 2.5 times as great as at rated full scale.
 
* Repeatability is consecutive runs with all conditions alike.
 
* Performance limits are for rated range. Turn down from rated range will cause a proportional increase in errors.

(1)
F.R. denotes Full Rated Range. F.S. denotes Full Scale Output. Additional Ranges available on request. Square Root Output available.

P1-P101

"Let us handle your pressure"


©2008 Tavis Corporation. All rights reserved. | Site by K&N Web Design | Sitemap